Aastra AXD Especificaciones Pagina 131

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 502
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 130
Installation and Maintenance Manual - Aastra 5000 AMT/PTD/PBX/0058/4/6/EN
Description des sous-ensembles 01/2011 Page 131
4.2.3.3 Monitoring
Two 5 A fuses located upstream from the rectifier are used to isolate the power supply
module in case of overvoltage.
An F300 (6.3 A) fuse inside the power supply module (see Figure 4.5 ) protects the power
supply in case of polarity inversion when connecting the battery.
The converter monitors the voltage on the battery terminals, and stops when this voltage
drops below a threshold set at 43V. This device prevents deep discharging of the battery
in the absence of mains or failure/shutdown of the rectifier.
When the 2 fans are detected as stopped simultaneously, the power supply is cut off
automatically; restarting is possible only through an On/Off sequence.
Figure 4.4 OVERVIEW OF THE ADS 350X MODULE
Vista de pagina 130
1 2 ... 126 127 128 129 130 131 132 133 134 135 136 ... 501 502

Comentarios a estos manuales

Sin comentarios